Resources

Conductor resistance tables

DC resistance of copper and aluminium conductors used by the GridCircuits voltage-drop calculator.

North American sizes (NEC)

Source: NEC (NFPA 70) Chapter 9, Table 8 — stranded, uncoated, 75 °C. Values in Ω/1000 ft.

SizeCopperAluminium
14 AWG3.14—
12 AWG1.983.25
10 AWG1.242.04
8 AWG0.7781.28
6 AWG0.4910.808
4 AWG0.3080.508
3 AWG0.2450.403
2 AWG0.1940.319
1 AWG0.1540.253
1/0 AWG0.1220.201
2/0 AWG0.09670.159
3/0 AWG0.07660.126
4/0 AWG0.06080.1
250 kcmil0.05150.0847
300 kcmil0.04290.0707
350 kcmil0.03670.0605
400 kcmil0.03210.0529
500 kcmil0.02580.0424
600 kcmil0.02140.0353
750 kcmil0.01710.0282
1000 kcmil0.01290.0212

Metric sizes (IEC)

Source: IEC 60228 — Class 2 stranded, maximum DC resistance at 20 °C. Values in Ω/km.

SizeCopperAluminium
1.5 mm²12.1—
2.5 mm²7.41—
4 mm²4.61—
6 mm²3.08—
10 mm²1.83—
16 mm²1.151.91
25 mm²0.7271.2
35 mm²0.5240.868
50 mm²0.3870.641
70 mm²0.2680.443
95 mm²0.1930.32
120 mm²0.1530.253
150 mm²0.1240.206
185 mm²0.09910.164
240 mm²0.07540.125
300 mm²0.06010.1
400 mm²0.0470.0778
500 mm²0.03660.0605
630 mm²0.02830.0469

Temperature correction

RT = R20 · [1 + α (T − 20)], with α = 0.00393 /°C for copper and 0.00403 /°C for aluminium.

Open the voltage drop calculator Download as CSV