Transmission & Grid calculator
Transformer Full-Load & Fault Current Calculator
Full-load current on both windings and the maximum available fault current at the secondary terminals, from kVA and percent impedance.
GridBasis: IEEE C57.12.00 · IEEE 141 (Red Book) · IEC 60909 (note)
Results
- Enter values to calculate
- —
Formula
Full-load current: three-phase IFL = kVA × 1000 / (√3 · V); single-phase IFL = kVA × 1000 / V
Maximum secondary fault current (infinite bus): ISC = IFL,sec × 100 / %Z
Fault level: MVASC = kVA / (%Z / 100) / 1000
Worked example
1000 kVA, 13.8 kV to 480 V, 5.75 %Z, three-phase: IFL,sec = 1,000,000 / (1.732 × 480) = 1203 A; IFL,pri = 41.8 A; ISC = 1203 × 100 / 5.75 = 20.9 kA.
Assumptions and standards
- Infinite-bus (unlimited source) method: it ignores utility source impedance, so it overstates the real fault current. That is conservative for equipment ratings.
- Motor contribution is not included; add it for a full study.
- IEC 60909 studies also apply a voltage factor c (typically 1.05 or 1.10 for low voltage) and the actual source impedance.
- Transformer impedance tolerance (often ±7.5 % of nameplate %Z) is not applied.
Formula and data last verified: October 2026.
Frequently asked questions
Why is the infinite-bus fault current higher than my study shows?
A full study includes the utility source impedance and cable impedance, which both reduce fault current. The infinite-bus value is the worst case and is useful for a quick equipment-rating check.
Where do I find %Z?
On the transformer nameplate or test report. Typical values range from about 2 % for small units to 5.75 % or more for large distribution transformers.
Can I use these results for final design?
Use them for preliminary design and checking. Final designs must be verified by a qualified engineer against the code edition and standards adopted where the work is installed.