Transmission & Grid calculator

Three-Phase Power Calculator

Convert between current, kW, kVA and kVAR for three-phase or single-phase systems at any voltage and power factor.

GridBasis: IEEE Std 100 definitions · IEC 60050

Inputs

A / kW / kVA
V
0–1

Results

Enter values to calculate
—

Formula

Three-phase: S = √3 · VLL · I   Single-phase: S = V · I

P = S · PF   Q = S · sin(arccos PF)   S² = P² + Q²

  • S apparent power (VA), P real power (W), Q reactive power (var)
  • VLL line-to-line voltage, PF displacement power factor

Worked example

480 V three-phase load drawing 100 A at 0.85 power factor: S = 1.732 × 480 × 100 = 83.1 kVA, P = 83.1 × 0.85 = 70.7 kW, Q = 83.1 × 0.527 = 43.8 kvar.

Assumptions and standards

  • Balanced, sinusoidal system. Harmonics are not included; with non-linear loads the true power factor is lower than the displacement power factor.
  • Three-phase voltage is line-to-line.

Formula and data last verified: October 2026.

Frequently asked questions

What is the difference between kW and kVA?

kW is real power that does work. kVA is apparent power, the product of voltage and current, which sizes cables, transformers and generators. They are related by the power factor: kW = kVA × PF.

Where does √3 come from?

In a balanced three-phase system, line-to-line voltage is √3 times the line-to-neutral voltage, so total power equals √3 × V(line-to-line) × I.

Can I use these results for final design?

Use them for preliminary design and checking. Final designs must be verified by a qualified engineer against the code edition and standards adopted where the work is installed.

Is my data sent anywhere?

No. Every calculation runs in your browser. Nothing you type is uploaded or stored on our servers.